5.5.5 Installation remote from lightweight partition and compartment walls with mineral
wool
Fig. 65: Installation with joint filler remote from a lightweight partition wall
1
FKRS-EU
2.19
Joint filler
3.2
Lightweight partition wall with metal support
structure, cladding on both sides
6.5
Mineral wool (depending on wall construction)
6.29
Mineral wool Paroc Hvac Fire Mat 80BLC
(80 kg/m³)
6.30
Reinforcing board mineral wool
Paroc Hvac Fire Mat 80BLC (80 kg/m³), glued all
round
9.2
Sheet steel duct
Up to EI 60 S
Fig. 66: Dry mortarless installation remote from a lightweight partition wall, with a fire batt
1
FKRS-EU
3.2
Lightweight partition wall with metal support
structure, cladding on both sides
6.5
Mineral wool (depending on wall construction)
6.7
Fire batt
6.29
Mineral wool Paroc Hvac Fire Mat 80BLC
(80 kg/m³)
6.30
Reinforcing board mineral wool
Paroc Hvac Fire Mat 80BLC (80 kg/m³), glued all
round
7.11
Trim panels, single-layer, fire-resistant
8.21
Acrylic or sealing compound (suitable for fire batt
system)
9.2
Sheet steel duct
Up to EI 60 S
Additional requirements: installation remote from lightweight partition and compartment walls with mineral
wool
Installation
Lightweight partition walls and compartment wall... > Installation remote from lightweight partition...
Fire damper Type FKRS-EU
81