5.4.2 Mortar-based installation – multiple occupancy of an installation opening
Fig. 31: Mortar-based installation – multiple occupancy of an installation opening
1
FKRS-EU
2.1
Mortar
3.1
Solid wall (load-bearing component)
4.1
Solid ceiling slab (load-bearing component)
Up to EI 90 S
Additional requirements: mortar-based installation – multiple occupancy of an installation opening
Solid wall
Size of the installation opening W
×
H
≤
1.2 m
2
The number of fire dampers is limited to 10 units in single or double-row arrangement
Installation
Solid walls > Mortar-based installation – multiple occupancy...
Fire damper Type FKRS-EU
43