5.5.2 Dry mortarless installation without installation kit
Fig. 56: Dry mortarless installation into a lightweight partition wall, without installation kit
1
FKRS-EU
2.19
Joint filler (filler, ready-to-use putty or equivalent)
3.2
Lightweight partition wall or compartment wall
with metal support structure or steel support
structure, cladding on both sides
6.5
Mineral wool (depending on wall construction)
7.13
Cladding, fire-resistant, also with sheet steel
insert
Up to EI 60 S
Additional requirements: dry mortarless installation into lightweight partition walls without installation kit
Lightweight partition wall
≥
200 mm distance between two fire dampers
≥
75 mm distance from fire damper to load-bearing structural elements
1.
Make a circular installation opening DN + 6 – 10 mm between two regular studs.
2.
Chamfer the outer layer of the cladding all round on both sides and completely fill the surrounding gap on both
sides with joint filler to the depth of the cladding.
Installation
Lightweight partition walls and compartment wall... > Dry mortarless installation without installati...
Fire damper Type FKRS-EU
72