5.5.7 Dry mortarless installation with fire batt
Fig. 69: Dry mortarless installation into a lightweight partition wall, with a fire batt
1
FKRS-EU
2.4
Fire batt with ablative coating
3.2
Lightweight partition wall or compartment wall
with metal support structure or steel support
structure, cladding on both sides
4.1
Solid ceiling slab
6.5
Mineral wool (depending on wall construction)
6.10
Ablative coating around the perimeter,
d = at least 2.5 mm
6.19
Mineral wool > 1000 °C, > 80 kg/m³,
thickness = 20 mm, leave out the actuator and
release mechanism; inspection openings must
remain accessible
6.20
Sleeve (can be ordered separately)
6.24
Elastomeric foam (flame-resistant, non-drip-
ping)
The following applies in Germany: For notes
on the use of elastomeric foams, see
.
7.10
Trim panels
7.13
Cladding, fire-resistant, also with sheet steel
insert
7.14
Reinforcing board of the same material as the
wall
*
6.19, 6.20 or 6.24 as an alternative
**
Installation near the floor analogous to
–
Note:
The fire resistance properties of depend on the nominal width and 6.10*.