Maintenance
•
Inspect both the main unit control panel and heat section control box for loose electrical
components and terminal connections, as well as damaged wire insulation. Make any
necessary repairs.
•
Gas Heat Units only - Check the heat exchanger for any corrosion, cracks, or holes.
•
Check the combustion air blower for dirt. Clean as necessary.
Note:
Typically, it is not necessary to clean the gas furnace. However, if cleaning does become
necessary, remove the burner inspection plate from the rear of the heat exchanger to access
the drum. Be sure to replace the existing gaskets with new ones before reinstalling the
inspection plate.
•
Open the main gas valve and apply power to the unit heating section; then initiate a “Heat” test
using the start-up procedure described in “Gas Furnace Start-Up”.
•
Verify that the ignition system operates properly.
Coil Cleaning
Regular coil maintenance, including annual cleaning enhances the unit’s operating efficiency by
minimizing:
•
compressor head pressure and amperage draw;
•
water carryover;
•
fan brake horsepower; and,
•
static pressure losses.
At least once each year—or more often if the unit is located in a “dirty” environment—clean the
evaporator, microchannel condenser, and reheat coils using the instructions outlined below. Be
sure to follow these instructions as closely as possible to avoid damaging the coils.
To clean refrigerant coils, use a soft brush and a sprayer.
Important:
DO NOT use any detergents with microchannel condenser coils. Pressurized water
or air ONLY.
For evaporator and reheat coil cleaners, contact the local Trane Parts Center for appropriate
detergents.
1.
Remove enough panels from the unit to gain safe access to coils.
Important:
Bridging between the main supports required before attempting to enter into the
unit. Bridging may consist of multiple 2 by 12 boards or sheet metal grating.
2. Straighten any bent coil fins with a fin comb.
NOTICE:
Coil Cleaners!
Coil cleaners can damage roofs, surrounding buildings, vehicles, etc. Cleaning substances
should be checked to ensure that they will not cause damage to surroundings. Coils and roof (if
applicable) should be rinsed thoroughly. Do not spray coil cleaners in windy conditions.
WARNING
No Step Surface!
Do not walk on the sheet metal base. Walking on the base could cause the supporting metal to
collapse, resulting in the operator/technician to fall. Failure to follow this recommendation
could result in death or serious injury.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...