Emergency Override Definitions (with LCI-I/BCI-I module installed)
When an LCI-I/BCI-I module is installed, the user can initiate one of five (5) Emergency Override
sequences that have the following predefined unit operation:
PRESSURIZE
–
Supply Fan - On
–
Inlet Vanes - Open (if equipped)
–
Exhaust/Return Fan - Off (if equipped)
–
Exhaust/Return Dampers - Closed (if equipped)
–
OA Dampers - Open
–
Heat - All heat stages Off (staged gas and elec.), Hydronic
–
Heat & Mod Gas Heat output at 0%.
–
Occupied/Unoccupied output - Energized
–
VO Relay - Energized (with VOM module installed)
–
OA Preheater State - Off (with VCM module installed)
DEPRESSURIZE
–
Supply Fan - Off
–
Inlet Vanes - Closed (if equipped)
–
Exhaust/Return Fan - On (if equipped)
–
Exhaust/Return Dampers -Open (if equipped)
–
OA Dampers - Closed
–
Heat - All heat stages Off (staged gas and elec.), Hydronic
–
heat & Mod Gas Heat output at 0%.
–
Occupied/Unoccupied output - De-energized
–
VO Relay - Energized (with VOM module installed)
–
OA Preheater State - Off (with VCM module installed)
PURGE
–
Supply Fan - On
–
Inlet Vanes - Open (if equipped)
–
Exhaust/Return Fan - On (if equipped)
–
Exhaust/Return Dampers - Open (if equipped)
–
OA Dampers - Open
–
Heat - All heat stages Off (staged gas and elec.), Hydronic
–
Heat & Mod Gas Heat output at 0%.
–
Occupied/Unoccupied output - Energized
–
VO Relay - Energized (with VOM module installed)
–
OA Preheater State - Off (with VCM module installed)
SHUTDOWN
–
Supply Fan - Off
–
Inlet Vanes - Closed (if equipped)
–
Exhaust/Return Fan - Off (if equipped)
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...