Installation
Table 22. Electrical service sizing data — motors — 20-130 tons
Nominal
Tons
Nominal Voltage
200
FLA
230
FLA
460
FLA
575
FLA
Air-Cooled Condenser Fan Motor
20
8.2
8.2
3.6
2.8
25
12.3
12.3
5.4
4.2
30
12.3
12.3
5.4
4.2
40
16.4
16.4
7.2
5.6
50, 55
24.6
24.6
10.8
8.4
60
24.6
24.6
10.8
8.4
70
24.6
24.6
10.8
8.4
75
24.6
24.6
10.8
8.4
90
N/A
N/A
14.4
11.2
105 N/A
N/A
18.0
14.0
115 N/A
N/A
18.0
14.0
130 N/A
N/A
21.6
16.8
Motor Horsepower
Supply/Exhaust/Return
2
Fan Motor
3
11.0
8.6
4.3
3.8
5
15.2
13.2
6.6
5.4
7½
21.5
18.8
9.4
7.5
10
29.0
25.2
12.6
10.1
15
40.7
37.8
18.9
15.1
20
56.1
49.4
24.7
19.6
25
70.5
62.0
31.0
24.5
30
85.5
73.2
36.6
29.2
40
(a)
(a) 40 Hp motor available as standard in 460 & 575 volt only.
N/A
N/A
47.6
39.0
Note:
Return fan motors are available in 3-20 Hp.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...