RT-SVX36G-EN
Unit Start Up
Note:
Important:
Do not operate the compressors for extended periods of time without the condenser
fans; high head pressure will develop.
GAS HEAT
(Full Capacity)
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
STAGE 1
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
STAGE 2
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
(High Fire Adjustment)
FULL MODULATING
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
(Low Fire Adjustment)
LIMITED MODULATING
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
(High Fire Adjustment)
LIMITED MODULATING
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
(Low Fire Adjustment)
ELECTRIC HEAT
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
Stage 1
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
Stage 2
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
Stage 3
Closed
Closed
100%
Unocc
OFF
OFF
OFF
OFF
HYDRONIC HEAT
Closed
Closed
0%
Default
OFF
OFF
OFF
OFF
PRE-HEATER
Closed
Closed
0%
Default
OFF
OFF
OFF
OFF
FRESH AIR DAMPERS
100%
Closed
0%
Default
OFF
OFF
OFF
OFF
Open
EXHAUST DAMPERS
100%
100%
0%
Default
OFF
OFF
OFF
OFF
Open
REHEAT
Cooling Valve
Closed
Closed
0%
Default
100-0
OFF
OFF
OFF
Reheat Valve
Closed
Closed
0%
Default
0-100
OFF
OFF
OFF
Pumpout Solenoid
Closed
Closed
0%
Default
ON
OFF
OFF
OFF
EVAP COND
Sump Pump
Closed
Closed
0%
Default
OFF
ON
OFF
ON
Sump Heater
Closed
Closed
100%
Default
OFF
OFF
ON
OFF
Table 36. Service test guide for component operation — Part II of II (continued)
Component
Being Tested
Component Configuration
Occ
Unocc
Relay
Reheat
Sump
Pump
Sump
Heater
Dolphin
Econo
Damper
Exhaust
Damper
VFD
Output
Table 37. Service test guide component operation—evaporative condenser
Component Being Tested
Requirements (ON)
Requirements (OFF)
Compressors
Sump minimum level switch must be closed for a minimum of five minutes No Requirements
Sump Pump
Sump minimum level switch must be closed for a minimum of five minutes No Requirements
Condenser Fans
No Requirements
No Requirements
Fill Valve Relay
No Requirements
No Requirements
Drain Valve Actuator
No Requirements
No Requirements
Sump Heater
No Requirements
No Requirements
Notes:
1.
Sump freeze protection is active during AUTO but is inactive in service test modes (head pressure control set to MANUAL).
2.
Water treatment drain request will be ignored in service test.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...