Installation
O/A Sensor & Tubing Installation
An Outside Air Pressure Sensor is shipped with all units designed to operate on variable air volume
applications, units equipped with a return fan, or constant volume units with 100% modulating
exhaust w/Statitrac.
On VAV systems, a duct pressure transducer (3U60) and the outside air sensor is used to control
the discharge duct static pressure to within a customer-specified parameter.
On CV & VAV units equipped with 100% modulating exhaust w/Statitrac, a space pressure
transducer (3U62) and the outside air sensor is used to control the exhaust fan and dampers to
relieve static pressure to within a customer-specified parameter within the controlled space.
On units equipped with a return fan, a return pressure transducer (3U106) is connected to the
O/A sensor for comparison with return plenum pressure.
Refer to
and the following steps to install the sensor and the pneumatic tubing.
1.
Remove the O/A pressure sensor kit located inside the filter section. The kit contains the
following items;
•
O/A static pressure sensor with sensor mounting
•
Bracket
•
50' of 3/16” O.D. pneumatic tubing
•
Mounting hardware
Figure 22. Removing supply and exhaust fan assembly shipping hardware (90-130 Ton)
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...