178
RT-SVX36G-EN
Maintenance
5. Remove the belt tension gauge. The small O-ring now indicates a number other than zero on
the plunger’s force scale. This number represents the force (in pounds) required to give the
needed deflection.
6. Compare the “force” scale reading (Step 5) with the appropriate “force” value listed in
. If the “force” reading is outside the range, readjust the belt tension.
Note:
Actual belt deflection “force” must not exceed the maximum “force” value shown in
7.
Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension will
decrease rapidly until the new belts are “run in”.
Table 65. Belt tension measurement and deflection ranges
Belts Cross
Section
Small P.D.
Range
Deflection Force (lbs.)
Steel Cable Gripbelts
Super Gripbelts
Gripnotch
Min.
Max.
Min
Max.
Min
Max
A
3.0 - 3.6
3
4 1/2
3 7/8
5 1/2
3 1/4
4
3.8 - 4.8
3 1/2
5
4 1/2
6 1/4
3 3/4
4 3/4
5.0 - 7.0
4
5 1/2
5
6 7/8
4 1/4
5 1/4
B
3.4 - 4.2
4
5 1/2
5 3/4
8
4 1/2
5 1/2
4.4 - 5.6
5 1/8
7 1/8
6 1/2
9 1/8
5 3/4
7 1/4
5.8 - 8.8
6 3/8
8 3/4
7 3/8
10 1/8
7
8 3/4
Belts Cross
Section
Small P.D.
Range
Deflection Force (lbs.)
358 Gripbelts
358 Gripnotch
Min.
Max.
Min
Max.
5V
4.4 - 8.7
—
—
10
15
7.1 - 10.9
10 1/2
15 3/4
12 7/8
18 3/4
11.8 - 16.0
13
19 1/2
15
22
Figure 91. Belt deflection
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...