14
RT-SVX36G-EN
General Information
Compressor Modules
(SCM & MCM - 1U49 standard on all units)
The compressor modules, (Single Circuit & Multiple Circuit), upon receiving a request for
mechanical cooling, energizes the appropriate compressors and condenser fans. It monitors the
compressor operation through feedback information it receives from various protection devices.
Human Interface Module
(HI - 1U65 standard on all units)
The Human Interface module enables the operator to adjust the operating parameters for the unit
using it's 16 key keypad. The 2 line, 40 character LCD screen provides status information for the
various unit functions as well as menus for the operator to set or modify the operating parameters.
Heat Module
(1U50 used on heating units)
The Heat module, upon receiving a request for Heating, energizes the appropriate heating stages
or strokes the Modulating Heating valve as required.
Table 1.
RTM Resistance Input vs. Setpoint Temperatures
RTM cooling or heating
setpoint input used
as the source for
a ZONE temp setpoint (°F)
RTM cooling setpoint input
used as the source
for SUPPLY AIR temp
setpoint cooling (°F)
Resistance (Ohms) Max.
Tolerance 5%
40
40
1084
45
45
992
50
50
899
55
55
796
60
60
695
65
65
597
70
70
500
75
75
403
80
80
305
n/a
85
208
n/a
90
111
Table 2.
RTM Resistance Value vs. System Operating Mode
Resistance applied to RTM MODE
input Terminals (Ohms)
Max. Tolerance 5%
Constant Volume Units
Fan Mode
System Mode
2320
Auto
Off
4870
Auto
Cool
7680
Auto
Auto
10770
On
Off
13320
On
Cool
16130
On
Auto
19480
Auto
Heat
27930
On
Heat
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...