80
RT-SVX36G-EN
Installation
–
Supply fan - OFF
–
Inlet Vanes/VFD - 0% (if equipped)
–
Exhaust/Return fan - ON, Exhaust/Return dampers - Open
–
O/A dampers - Closed
–
Heat - All stages OFF, Modulating Heat output at 0 VDC
–
Occupied/Unoccupied output - De-energized (Occupied)
–
VO Relay - Energized
–
Pre-heater State - Off (if equipped)
•
VOM Mode “D” Priority 4 - Purge:
–
Supply fan - ON
–
Inlet Vanes/VFD - 100% (if equipped)
–
Exhaust/Return fan - ON, Exhaust/Return dampers - Open
–
O/A dampers - Open
–
Heat - All stages OFF, Modulating Heat output at 0 VDC
–
Occupied/Unoccupied output - Energized (Unoccupied)
–
VO Relay - Energized
–
Pre-heater State - Off (if equipped)
•
VOM Mode “E” Priority 5 - Purge with duct pressure control:
–
Supply fan - ON
–
Inlet Vanes/VFD - (if equipped) Controlled by S/A Pressure Control with supply air pressure
high limit disabled.
–
Exhaust/Return fan - ON, Exhaust/Return dampers - Open
–
O/A dampers - Open
–
Heat - All stages OFF, Modulating Heat output at 0 VDC
–
Occupied/Unoccupied output - Energized (Unoccupied)
–
VO Relay - Energized
–
Pre-heater State - Off (if equipped)
“OFF” - will appear in the Ventilation Override screen after all VOM binary inputs have been reset
(opened).
Due to codes in some areas, the definitions for some or all of the VOM modes may have to be locked
into the program by the user. Once the definitions are locked, the Ventilation Override Module must
be replaced in order to reprogram that sequence.
Refer to
for the proper connection terminals in the unit control
panel for each of the VOM initiating device’s and the appropriate Programming, Troubleshooting
Guide (PTG Latest Edition) for programming instructions.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...