Unit Start Up
•
Using the UP and DOWN arrows go to Chan 1 Cell: Standard. Ensure this channel is set to
standard
•
If not press the RIGHT arrow key and set to standard then press the ENTER key to return to the
CALIBRATION menu
•
Using the UP and DOWN arrows go to Chan 1 Cell. Ensure that the cell constant is set to 1.0
•
If not press the RIGHT arrow key and set the cell constant to 1.0 then press the ENTER key to
return to the CALIBRATION menu
•
Using the UP and DOWN arrows go to Chan 1 Set: Temperature and press the RIGHT arrow key
to enter the edit mode
•
Adjust the temperature on the controller to match the actual temperature
•
Press the ENTER key to save the input and return to the CALIBRATE menu
•
Using the UP and DOWN arrows, go to the Chan 1 Set: Conductivity and press the RIGHT arrow
key to enter the edit mode
•
Adjust the conductivity on the controller to match the actual conductivity rating of the liquid
•
Press the ENTER key to save the conductivity rating and return to the CALIBRATE menu
•
When finished calibrating the controller, press the UP and DOWN key simultaneously to return
to normal operating mode
Procedure to set purge setpoints on the conductivity controller
Note:
Visit this webpage for additional documentation: <http://www.gfsignettools.com/products/
pdf/8860eng.pdf>
•
Work with local water treatment expert to identify nominal purge and emergency purge
conductivity value.
•
Close the ball valve on the chemical treatment tree and remove the conductivity sensor from
the tree.
•
Enter Service test mode on the unit HI and energize the sump pump, ensuring the compressors
are set to “OFF”
•
With the conductivity controller connected to the sensor and power, enter the CALIBRATE menu
by holding down the enter key for 2 seconds
•
When asked for the calibration key code, hit the UP-UP-UP-DOWN arrow keys in sequence
•
Using the UP and DOWN arrows, go to Relay 1 Setpoint: and press the RIGHT arrow key to enter
edit mode (K1)
•
Adjust the set point to the nominal blowdown conductivity value
•
Press the ENTER key to return to the CALIBRATE menu
•
Using the UP and DOWN arrows, go to Relay 2 Setpoint: and press the RIGHT arrow key to enter
edit mode (K2)
•
Adjust the set point to the emergency conductivity value
•
Press the ENTER key to return to the CALIBRATE menu
•
When finished setting the values, press the UP and DOWN key simultaneously to return to
normal operating mode
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...