RT-SVX36G-EN
135
Unit Start Up
Table 49. Fresh air damper pressure drop (inches w.c.) — Air-Cooled and Evaporative Condensing
(20, 25 Ton and 24, 29 Ton) Units
(50, 55 and 59 Ton) Units
CFM
Damper Position
CFM
Damper Position
#1
#2
#3
#4
#5
#6
#1
#2
#3
#4
#5
#6
4000
0.03
0.04
0.06
0.13
0.16
0.33
10000
0.03
0.04
0.09
0.18
0.23
0.55
6000
0.03
0.04
0.10
0.20
0.30
0.90
14000
0.09
0.12
0.20
0.35
0.50
1.36
8000
0.19
0.21
0.32
0.52
0.75
1.75
18000
0.31
0.36
0.50
0.79
1.10
-
9000
0.30
0.35
0.48
0.76
1.08
2.40
20000
0.45
0.51
0.70
1.05
1.57
-
10000
0.45
0.51
0.70
1.05
1.57
-
22000
0.58
0.66
0.75
1.30
1.95
-
11000
0.62
0.71
0.95
1.42
2.15
-
24000
0.75
0.88
1.10
1.75
2.50
-
(30, 36 Ton) Units
(60, 70, 75 Ton and 73, 80, 89 Ton) Units
CFM
Damper Position
CFM
Damper Position
#1
#2
#3
#4
#5
#6
#1
#2
#3
#4
#5
#6
6000
0.03
0.04
0.07
0.15
0.20
0.43
14000
0.03
0.04
0.12
0.25
0.35
1.05
8000
0.03
0.05
0.11
0.21
0.30
0.90
18000
0.19
0.21
0.32
0.52
0.75
1.75
10000
0.15
0.19
0.26
0.43
0.62
1.50
22000
0.45
0.51
0.70
1.05
1.57
-
11000
0.20
0.25
0.37
0.60
0.85
1.85
26000
0.70
0.80
1.02
1.58
2.30
-
12000
0.31
0.36
0.50
0.79
1.10
2.40
28000
0.88
1.03
1.30
2.20
-
-
13000
0.42
0.48
0.62
0.97
1.42
-
30000
1.05
1.22
1.55
2.65
-
-
(40, 48 Ton) Units
(90 - 130 Ton) Units
CFM
Damper Position
CFM
Damper Position
#1
#2
#3
#4
#5
#6
#1
#2
#3
#4
#5
#6
8000
0.03
0.04
0.08
0.16
0.21
0.52
27000
0.31
0.36
0.50
0.79
1.10
2.40
10000
0.03
0.05
0.11
0.21
0.30
0.90
32000
0.55
0.64
0.72
1.25
1.88
-
12000
0.10
0.13
0.21
0.38
0.55
1.40
36000
0.75
0.88
1.10
1.75
2.50
-
14000
0.20
0.25
0.37
0.60
0.85
1.85
40000
1.00
1.18
1.50
2.50
-
-
16000
0.41
0.46
0.60
0.94
1.38
-
43000
1.20
1.42
1.92
-
-
-
18000
0.56
0.65
0.74
1.28
1.92
-
46000
1.40
1.58
2.29
-
-
-
NOTICE:
Compressors Failure!
Unit must be powered and crankcase heaters energized at least 8 hours BEFORE compressors
are started. This will protect the compressors from premature failure.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...