RT-SVX36G-EN
131
Unit Start Up
Table 46. Return fan performance—40, 50, 55 tons AC; 48, 59 tons EC (27”)
CFM
Negative Static Pressure
Std.
0.25
0.50
0.75
1.00
1.25
1.50
1.75
2.00
Air
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
7500
709
0.82
766
1.16
815
1.50
861
1.85
906
2.22
949
2.60
991
2.99
1033
3.39
8000
748
0.95
803
1.31
851
1.67
895
2.04
938
2.43
979
2.82
1018
3.22
1058
3.64
8500
788
1.09
840
1.47
887
1.86
930
2.24
971
2.64
1010
3.05
1049
3.48
1087
3.92
9000
827
1.24
878
1.64
924
2.05
965
2.46
1005
2.88
1043
3.31
1080
3.75
1115
4.19
9500
867
1.41
916
1.83
961
2.27
1001
2.70
1040
3.14
1076
3.58
1112
4.03
1146
4.50
10000
908
1.60
955
2.04
999
2.50
1038
2.95
1075
3.41
1111
3.88
1145
4.34
1179
4.83
10500
948
1.81
994
2.27
1036
2.75
1075
3.23
1111
3.70
1145
4.18
1179
4.68
1212
5.18
11000
989
2.04
1033
2.51
1074
3.01
1112
3.51
1147
4.01
1181
4.51
1213
5.02
1245
5.53
11500
1030
2.28
1072
2.78
1112
3.29
1149
3.82
1184
4.33
1216
4.86
1248
5.38
1279
5.92
12000
1071
2.55
1112
3.06
1151
3.59
1187
4.14
1221
4.69
1253
5.24
1284
5.78
1314
6.33
12500
1112
2.83
1152
3.37
1189
3.92
1225
4.48
1258
5.06
1290
5.62
1320
6.19
1349
6.76
13000
1153
3.14
1192
3.70
1228
4.27
1263
4.86
1296
5.45
1327
6.04
1356
6.63
1385
7.23
13500
1194
3.47
1232
4.05
1267
4.63
1301
5.24
1333
5.85
1364
6.47
1393
7.08
1421
7.70
14000
1236
3.83
1272
4.42
1307
5.03
1340
5.66
1371
6.29
1401
6.94
1430
7.57
1457
8.20
14500
1277
4.21
1313
4.82
1346
5.45
1379
6.10
1410
6.75
1439
7.42
1467
8.08
1494
8.73
15000
1319
4.62
1353
5.25
1386
5.90
1417
6.55
1448
7.23
1477
7.92
1504
8.61
1531
9.29
15500
1361
5.05
1394
5.71
1426
6.37
1457
7.05
1486
7.74
1514
8.44
1542
9.16
1569
9.87
16000
1402
5.51
1435
6.18
1466
6.87
1496
7.57
1525
8.28
1553
9.01
1580
9.74
1606
10.47
16500
1444
6.00
1476
6.69
1506
7.40
1535
8.12
1564
8.85
1591
9.58
1617
10.34
1643
11.10
17000
1486
6.52
1517
7.23
1547
7.96
1575
8.70
1603
9.44
1629
10.20
1655
10.97
1681
11.75
17500
1528
7.07
1558
7.80
1587
8.55
1615
9.30
1642
10.07
1668
10.85
1694
11.64
1718
12.43
18000
1570
7.65
1599
8.40
1627
9.17
1655
9.94
1681
10.73
1707
11.53
1732
12.33
1757
13.15
18500
1612
8.26
1640
9.03
1668
9.81
1695
10.62
1721
11.43
1746
12.23
1771
13.07
1794
13.89
19000
1654
8.91
1682
9.70
1709
10.50
1735
11.31
1760
12.14
1785
12.97
1809
13.82
1833
14.67
19500
1696
9.59
1723
10.40
1749
11.22
1775
12.06
1800
12.90
1825
13.76
1848
14.62
1872
15.50
20000
1738
10.30
1765
11.13
1790
11.97
1816
12.83
1840
13.69
1864
14.56
1888
15.46
1910
16.34
20500
1780
11.05
1806
11.90
1831
12.76
1856
13.63
1880
14.52
1903
15.41
1926
16.31
1949
17.22
21000
1822
11.84
1848
12.71
1872
13.59
1897
14.48
1920
15.39
1943
16.29
1966
17.23
1988
18.14
21500
1864
12.66
1889
13.55
1914
14.45
1937
15.36
1960
16.29
1983
17.22
2005
18.16
2027
19.11
22000
1899
13.05
1926
14.11
1952
15.16
1977
16.20
2001
17.23
2024
18.24
2047
19.27
2069
20.28
22500
1941
13.91
1967
14.98
1992
16.05
2017
17.12
2041
18.19
2064
19.23
2086
20.27
2108
21.31
Notes:
1.
Max fan RPM 1981 For 27" Class II Fan
2.
Max Motor Available 15 HP For 27" Fan Size
3.
Max motors Available are as follows: 40T: 10 HP & 50/55T: 15 HP
4.
Max CFM is as follows: 40T: 18000, 50/55T: 22500)
5.
Min CFM is as follows: 40T: 7500 & 50/55T: 9000
6.
Return fan belt drive RPM selections will be available to cover 700-1900 RPM range +/- 50 RPM
7.
Performance data includes cabinet and rain hood effect. Damper pressure drop will have to be added to the return duct static per
Table 40, p. 126
8.
Shaded area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...