RT-SVX36G-EN
133
Unit Start Up
dampers are closed, can overload the supply fan motor and cause building pressurization control
problems due to improper CFM being delivered to the space.
The fresh air/return air damper linkage is connected to a crank arm with a series of holes that allows
the installer or operator to modify the amount of fresh air damper travel in order to match the return
static pressure. Refer to
for the equivalent return air duct losses that correspond to each of the holes
illustrated in
.
To Adjust the Fresh Air Damper Travel:
1.
Drill a 1/4” hole through the unit casing up stream of the return air dampers. Use a location that
will produce an accurate reading with the least amount of turbulence. Several locations may
be necessary, and average the reading.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1 OR UNIT DISCONNECT SWITCH 1S14.
2. Close the disconnect switch or circuit protector switch that provides the supply power to the
unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14.
3. Turn the 115 volt control circuit switch 1S1 and the 24 volt control circuit switch 1S70 to the “On”
position.
4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer to the latest edition of the applicable
programming manual for CV or VAV applications for the SERVICE TEST screens and
programming instructions.
5. Use
Table 35, p. 108
to program the following system components for operation by scrolling
through the displays;
–
Supply Fan (On)
–
Variable Frequency Drive (100% Output, if applicable)
–
RTM Occ/Unocc Output (Unoccupied)
–
Fresh Air Dampers (Closed)
6. Once the configuration for the components is complete, press the NEXT key until the LCD
displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test
is to start. This service test will begin after the TEST START key is pressed and the delay
designated in this step has elapsed. Press the ENTER key to confirm this choice.
7.
Press the TEST START key to start the test. Remember that the delay designated in step 6 must
elapse before the fan will begin to operate.
8. With the fresh air dampers fully closed and the supply fan operating at 100% airflow
requirements, measure the return static pressure at the location determined in step 1.
9. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan
operation.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...