RT-SVX36G-EN
43
Installation
Table 13. Evaporative condenser - approximate operating weights (lbs/kg)
Without Exhaust Fan
With Exhaust Fan
Unit
SX
SE
SF
SL/SS
SX
SE
SF
SL/SS
24
lbs
6549
6679
6944
6763
6907
7037
7302
7121
kg
2971
3030
3150
3068
3133
3192
3312
3230
29
lbs
6599
6729
6994
6813
6963
7093
7358
7177
kg
2993
3052
3172
3090
3158
3217
3338
3255
36
lbs
7121
7251
7513
7335
7538
7668
7933
7752
kg
3230
3289
3409
3327
3419
3478
3598
3516
48
lbs
9001
9156
9631
9359
9585
9740
10215
9943
kg
4083
4153
4369
4245
4348
4418
4633
4510
59
lbs
9213
9368
9843
9571
9856
10011
10486
10214
kg
4179
4249
4465
4341
4471
4541
4756
4633
73
lbs
11303
11458
11933
11691
12128
12283
12758
12516
kg
5127
5197
5413
5303
5501
5571
5787
5677
80
lbs
11430
11585
12060
11818
12255
12410
12885
12643
kg
5185
5255
5470
5361
5559
5629
5845
5735
89
lbs
11820
11975
12450
12208
12645
12800
13275
13033
kg
5361
5432
5647
5537
5736
5806
6021
5912
Notes:
1.
Weights shown for evaporative condensing units include the following features: high capacity evaporative coil. Add 520 lbs for 24, 29, 36, 48 and 59
units and 680 lbs for 73, 80 and 89 units for installed sump base water weight for evaporative condenser total operating weight.
2.
Weights shown represent approximate operating weights and have a ±5% accuracy. To calculate weight for a specific unit configuration, utilize TOPSS
or contact the local Trane sales representative. ACTUAL WEIGHTS ARE STAMPED ON THE UNIT NAMEPLATE.
Table 14. Roof curb max weight
(a)
Unit
Roof Curb Max. Weight
Unit
Roof Curb Max. Weight
SAHL
S*HL
SAHL
S*HL
20/24
490
510
70/80
610
640
222
231
277
290
25/29
490
510
75/89
610
640
222
231
277
290
30/36
490
510
90
N/A
770
222
231
N/A
349
40/48
515
550
105
N/A
770
234
249
N/A
349
50/55/59
515
550
115
N/A
770
234
249
N/A
349
60/73
515
550
130
N/A
770
234
249
N/A
349
(a) Roof curb weights include the curb and pedestal.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...