RT-SVX36G-EN
129
Unit Start Up
70/75
80/89
4000
271
0.29
364
0.54
438
0.82
499
1.07
550
1.30
601
1.56
651
1.87
6000
339
0.71
391
0.90
456
1.22
517
1.60
572
2.01
622
2.43
668
2.85
8000
425
1.55
460
1.73
497
1.96
542
2.30
591
2.72
639
3.20
684
3.73
10000 517
2.88
543
3.13
571
3.34
600
3.59
632
3.94
668
4.37
707
4.87
12000 612
4.84
633
5.15
655
5.43
678
5.68
702
5.95
726
6.29
752
6.71
13000 659
6.09
679
6.44
699
6.76
720
7.04
741
7.31
Note:
Shaded areas indicate non-standard drive selections. These drive selections must be manually factory selected.
Table 43. 20-89 tons - 50% exhaust fan performance
Table 44. 90-130 Tons - 50% exhaust fan performance
Cfm
Negative Static Pressure (In. W.G.)
Nom
Std
0.250
0.500
0.750
1.000
1.250
1.500
1.750
2.000
2.250
2.500
Tons
Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
90-130
12000 452 3.68 495
4.21
536 4.85 576 5.46 614 6.17 651 6.95 687 7.73 722 8.55 759 9.46 797 10.45
14000 516 5.71 551
6.21
586 6.85 622 7.63 657 8.36 690 9.09 723 9.96 754 10.88 785 11.79 815 12.72
16000 583 8.41 609
8.85
643 9.57 672 10.29 704 11.18 735 12.07 764 12.84 793 13.72 822 14.72 850 15.76
18000 650 11.88 672 12.29 699 12.94 729 13.79 755 14.59 782 15.56 811 16.62 838 17.53 864 18.41 889 19.39
20000 718 16.20 737 16.62 758 17.18 785 18.03 811 18.97 835 19.86 859 20.87 885 22.05 910 23.18 934 24.17
Note:
Shaded areas indicate non-standard drive selections. These drive selections must be manually factory selected.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...