Installation
–
Exhaust/Return Dampers - Closed (if equipped)
–
OA Dampers - Closed
–
Heat - All heat stages Off (staged gas and elec.), Hydronic
–
Heat & Mod Gas Heat output at 0%.
–
Occupied/Unoccupied output - De-energized
–
VO Relay - Energized (with VOM module installed)
–
OA Preheater State - Off (with VCM module installed)
FIRE
–
Supply Fan - Off
–
Inlet Vanes - Closed (if equipped)
–
Exhaust/Return Fan - Off (if equipped)
–
Exhaust/Return Dampers - Closed (if equipped)
–
OA Dampers - Closed
–
Heat - All heat stages Off (staged gas and elec.), Hydronic
–
Heat & Mod Gas Heat output at 0%.
–
Occupied/Unoccupied output - De-energized
–
VO Relay - Energized (with VOM module installed)
–
OA Preheater State - Off (with VCM module installed)
The UCM network relies on various sensors located throughout the system to provide temperature
information in the form of an analog input. All of the sensors used have the same temperature vs.
resistance co-efficient and are made from Keystone Carbon D97 material with a 1 degree
Centigrade tolerance.
Table 30. Temperature vs. resistance coefficient
Temperature (°F)
Resistance
(in. 1000 Ohms)
Temperature (°F)
Resistance
(in. 1000 Ohms)
-40
346.1
71
11.6
-30 241.7 72 11.31
-20 170.1 73 11.03
-10 121.4 74 10.76
-5 103 75 10.5
0 87.56 76 10.25
5 74.65 77 10
10 63.8 78 9.76
15 54.66 79 9.53
20 46.94 80 9.3
25 40.4 85 8.25
30 34.85 90 7.33
35 30.18 100 5.82
40 26.22 105 5.21
45 22.85 110 4.66
50 19.96 120 3.76
55 17.47 130 3.05
60 15.33 140
2.5
65 13.49 150
2.05
66 13.15 160 1.69
67 12.82 170 1.4
68 12.5 180 1.17
69 12.19 190
0.985
70 11.89 200 0.83
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...