RT-SVX36G-EN
27
General Information
terminate setpoint, the heat will turn off when the occ zone heat setpoint is reached, but it will stay
in DWU mode and cycle the heat to maintain setpoint.
Unoccupied Heating - Zone Temperature
When a Discharge Temperature Control unit is equipped with gas, electric, or hydronic heat and is
in the unoccupied mode, the zone temperature will be controlled to within the customers specified
setpoint deadband. During an unoccupied mode for a VAV unit, the VAV box/unocc relay will be in
the unoccupied position and the VFD/IGV output will be at 100%. This means that if there is a call
for heat (or cool) and the supply fan comes on, it will be at full airflow and the VAV boxes in the
space will need to be 100% open as signaled by the VAV box/unocc relay.
Supply Air Tempering
On Discharge Temperature Control units equipped with “Modulating Heat”, if the supply air
temperature falls 10°F below the supply air temperature setpoint, the hydronic heat valve will
modulate to maintain the supply air temperature to within the low end of the setpoint deadband.
Supply Duct Static Pressure Control (Occupied)
The RTM relies on input from the duct pressure transducer when a unit is equipped with Inlet Guide
Vanes or a Variable Frequency Drive to position the Inlet Guide Vanes or set the supply fan speed
to maintain the supply duct static pressure to within the static pressure setpoint deadband. See
.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...