68
RT-SVX36G-EN
Installation
Electric Heat Units (SEH_)
SEHL (20 through 89 Ton) electric heat units operating on 200/230 volts require two power supplies
as illustrated in
. Unless the unit was ordered with the optional factory mounted non-
fused disconnect switches, two field-supplied disconnect switches must be installed. The power
wires for the electric heat is routed into the electric heat control panel using the thru-the-base
access provided in the heating section. Refer to the appropriate illustration in
Base layout and Electrical Entrance diagram), for dimensional data.
On 20-130 ton units operating on 460/575 volts, only one power entry is required, as illustrated in
Use the information provided in
Table 21, p. 71
and the “Power Wire Sizing & Protection Device
Equations”, to determine the appropriate wire size and Maximum Over current Protection for the
heaters/unit.
Note:
Each power supply must be protected from short circuit and ground fault conditions. To
comply with NEC, protection devices must be sized according to the “Maximum Over
current Protection” (MOP) or “Recommended Dual Element” (RDE) fuse size data on the
unit nameplate.
Provide grounding for the supply power circuit in the electric heat control box.
Main Unit Power Wiring
lists the field connection wire ranges for both the main power terminal block 1TB1
and the optional main power disconnect switch 1S14.
Table 21, p. 71
lists the component electrical
data for 20 through 130 ton units. The electrical service must be protected from over current and
short circuit conditions in accordance with NEC requirements. Protection devices must be sized
according to the electrical data on the nameplate. Refer to the “Power Wire Sizing & Protection
Device Equations”, for determining;
a. the appropriate electrical service wire size based on “Minimum Circuit Ampacity” (MCA),
b. the “Maximum Over current Protection” (MOP) device,
c. the “Recommended Dual Element fuse size” (RDE).
1.
If the unit is not equipped with an optional factory installed non-fused disconnect switch, a field
supplied disconnect switch must be installed at or near the unit in accordance with the National
Electrical Code (NEC latest edition). Refer to the “Power Wire Sizing & Protection Device
Equations” (DSS calculation), for determining the correct size.
2. Location for the electrical service entrance is illustrated in
. Complete the unit's
power wiring connections onto either the main terminal block 1TB1, or the factory mounted
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST
follow requirements for field wiring installation and grounding as described in NEC and your
local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST
follow requirements for field wiring installation and grounding as described in NEC and your
local/state electrical codes. Failure to follow code could result in death or serious injury.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...