90
RT-SVX36G-EN
Installation
Table 31. GBAS Voltage vs. Setpoint
Setpoint
GBAS 0-5 VDC
GBAS 0-10 VDC
Valid Range
Occ Zone Cooling Setpoint(CV only)
0.5 to 4.5 VDC
0.5 to 9.5 VDC
50 to 90°F
Unocc Zone Cooling Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
50 to 90°F
Occ Zone Heating Setpoint(CV only)
0.5 to 4.5 VDC
0.5 to 9.5 VDC
50 to 90°F
Unocc Zone Heating Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
50 to 90°F
SA Cooling Setpoint (VAV only)
0.5 to 4.5 VDC
0.5 to 9.5 VDC
40 to 90°F
SA Cooling Setpoint (SZVAV only)
0.5 to 4.5 VDC
0.5 to 9.5 VDC
40 to 70°F
Zone Cooling Setpoint (SZVAV only)
0.5 to 4.5 VDC
0.5 to 9.5 VDC
50 to 80°F
Zone/Return Critical Temperature Setpoint (RR only)
0.5 to 4.5 VDC
0.5 to 9.5 VDC
75 to 95°F
SA Heating Setpoint (VAV only)
0.5 to 4.5 VDC
0.5 to 9.5 VDC
40 to 180°F
SA Heating Setpoint (SZVAV only)
0.5 to 4.5 VDC
0.5 to 9.5 VDC
65 to 95°F
Space Static Pressure Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
-0.20 to 0.30 IWC
SA Static Pressure Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
0.7 to 5.1 IWC
Min OA Flow Setpoint 1
0.5 to 4.5 VDC
0.5 to 9.5 VDC
0 to Unit Max Flow
MWU Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
50 to 90°F
Econ Dry Bulb Enable Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
50 to 140°F
SA_Reheat_Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
60 to 90°F
Minimum Position Setpoint 3
0.5 to 4.5 VDC
0.5 to 9.5 VDC
0 to 100%
Occ Dehumidification Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
40 to 65%
Unocc Dehumidification Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
40 to 65%
Occ Humidification Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
20 to 50%
Unocc Humidification Setpoint
0.5 to 4.5 VDC
0.5 to 9.5 VDC
20 to 50%
Notes:
1.
If DCV is enabled this is used for Design Minimum OA Flow Setpoint
2.
If DCV is enabled, this is used for Design Minimum OA Damper Position Setpoint
Table 32. GBAS 0-10 VDC output range
Setpoint
GBAS 0-10 VDC
Valid Range
Outdoor Air Temperature
0.5 to 9.5 VDC
-40 to 200°F
Zone Temperature
0.5 to 9.5 VDC
-40 to 200°F
Supply Air Temperature (VAV and CV
Discharge Temperature Control only)
0.5 to 9.5 VDC
-40 to 200°F
Supply Air Pressure (VAV only)
0.5 to 9.5 VDC
0.0 to 7.91 wc
Space Pressure
0.5 to 9.5 VDC
-0.67-0.67 wc
Space RH
0.5 to 9.5 VDC
0-100%
OA RH
0.5 to 9.5 VDC
0-100%
Space CO2 Level
0.5 to 9.5 VDC
50-2000 PPM
Cooling Capacity %
0.5 to 9.5 VDC
0-100%
Heating Capacity %
0.5 to 9.5 VDC
0-100%
Outdoor Air Damper Position
0.5 to 9.5 VDC
0-100%
Outdoor Airflow
0.5 to 9.5 VDC
0 to 65,000 CFM
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...