42
RT-SVX36G-EN
Installation
Table 12. Air-cooled condenser - approximate operating weights (Lbs./Kg)
Unit
Without Exhaust Fan
With Exhaust Fan
SA
SX
SE
SF
SL/SS
SA
SX
SE
SF
SL/SS
20
Lb
4092
4422
4712
4422
4312
4390
4720
5010
4720
4610
Kg
1856
2006
2137
2006
1956
1991
2141
2272
2141
2091
25
Lb
4181
4521
4791
4521
4391
4485
4825
5095
4825
4695
Kg
1896
2050
2173
2050
1992
2034
2188
2311
2188
2129
30
Lb
4572
4932
5202
4932
4812
5029
5389
5659
5389
5269
Kg
2074
2237
2359
2237
2183
2281
2444
2567
2444
2390
40
Lb
6433
6737
7217
6737
6577
7103
7407
7887
7407
7247
Kg
2918
3056
3273
3056
2983
3222
3360
3577
3360
3287
50
Lb
7175
7725
8185
7725
7555
7894
8444
8904
8444
8274
Kg
3255
3504
3713
3504
3427
3581
3830
4039
3830
3753
55
Lb
7425
7975
8455
7975
7815
8144
8694
9174
8694
8534
Kg
3368
3617
3835
3617
3545
3694
3944
4161
3944
3871
60
Lb
8338
8658
9118
8658
8498
9282
9602
10062
9602
9442
Kg
3782
3927
4136
3927
3855
4210
4355
4564
4355
4283
70
Lb
8604
8666
9146
8666
8516
9547
9609
10089
9609
9459
Kg
3903
3931
4148
3931
3863
4330
4358
4576
4358
4290
75
Lb
8843
9173
9653
9173
9023
9786
10116
10596
10116
9966
Kg
4011
4161
4379
4161
4093
4439
4589
4806
4589
4521
90
Lb.
N/A
13100
13250
13890
13370
N/A
14440
14590
15230
14710
Kg
N/A
5955
6023
6314
6077
N/A
6564
6632
6923
6686
105
Lb.
N/A
13710
13860
14500
13980
N/A
15050
15200
15840
15320
Kg
N/A
6232
6300
6591
6355
N/A
6841
6909
7200
6964
115
Lb.
N/A
13900
14080
14740
14100
N/A
15240
15420
16080
15440
Kg
N/A
6318
6400
6700
6409
N/A
6927
7009
7309
7018
130
Lb.
N/A
14350
14510
15150
14540
N/A
15690
15850
16490
15880
Kg
N/A
6523
6595
6886
6609
N/A
7132
7205
7495
7218
Notes:
1.
Weights shown for air-cooled units include the following features: standard coils, 100% economizer, throwaway filters, maximum motor sizes, 460V
XL, high heat.
2.
Weights shown represent approximate operating weights and have a ±5% accuracy. To calculate weight for a specific unit configuration, utilize
TOPSS™ or contact the local Trane sales representative. ACTUAL WEIGHTS ARE STAMPED ON THE UNIT NAMEPLATE.
Содержание IntelliPak SAHL Series
Страница 47: ...RT SVX36G EN 47 Installation Figure 16 Unit rigging Figure 17 Typical unit base and roof curb cross section...
Страница 65: ...RT SVX36G EN 65 Installation Figure 30 Hot Water Piping 90 130 Ton Figure 31 Steam Coil Piping 20 36 Ton...
Страница 86: ...86 RT SVX36G EN Installation Figure 38 Field connection diagram notes for 20 89 ton CV or VAV applications...
Страница 87: ...RT SVX36G EN 87 Installation Figure 39 Typical field wiring diagram for 20 89 ton VAV control option 2307 9177...
Страница 88: ...88 RT SVX36G EN Installation Figure 40 Typical field wiring diagram for 20 89 ton VAV control option...
Страница 173: ...RT SVX36G EN 173 Startup Checklists Figure 88 Dry bulb changeover map...
Страница 175: ...RT SVX36G EN 175 Maintenance Figure 89 Unit internal fuse replacement data for air handling units...