Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
245
Data
Description
Data type
Soft Output Characteristics Output 1 (0/255)
Soft output characteristic of output 1 of the
SITOP PSU8600 is activated.
Unsigned8
Reserved DipSwitch 7 (0/255)
Status of the reserved (unassigned) DIP switch 7. Unsigned8
Webserver Enable DipSwitch (0/255)
Actual switch position for activating/deactivating
the web server:
•
0 = web server deactivated
•
255 = web server activated
Unsigned8
Reset_In-Input (0/255)
Status of input "Reset_In": This input resets all
active faults and reactivates all of the outputs that
are in the "Ready for restart" operating state.
Unsigned8
Utarget Potentiometer [10mV]
Manually set setpoint of the output voltage at out-
put 1: Setpoint of the output voltage for an output
manually set using the potentiometer at the device;
in normal operation, the output is controlled to this
setpoint voltage.
Unsigned16
Ilimit potentiometer [mA]
Manually set threshold of the output current at
output 1. Response threshold of the output current
for an output set using the potentiometer at the
device. When this is exceeded, the output current
is interpreted as having an overload condition and
is shut down with a time delay - or limited.
The response threshold is set in the following
steps depending on the maximum output current:
•
Output current 20 A: 20 mA (0.02 A)
•
Output current 40 A: 40 mA (0.04 A)
Values that deviate from this grid are rounded off
to the next permissible value in the device.
Unsigned16
Output Enable manual button (0/255)
Actual DIP switch state for output 1:
•
0 = Manually switched off
•
255 = manually switched on
Unsigned8
Fill byte(s)
-
Unsigned8
ModuleIdentNumber slot0/MainUnit
Module identification number for slot 0 (basic unit). Unsigned32
ModuleIdentNumber slot 1
Module identification number for slot 1.
Unsigned32
ModuleIdentNumber slot 2
Module identification number for slot 2.
Unsigned32
ModuleIdentNumber slot 3
Module identification number for slot 3.
Unsigned32
ModuleIdentNumber slot 4
Module identification number for slot 4.
Unsigned32
ModuleIdentNumber slot 5
Module identification number for slot 5.
Unsigned32
ModuleIdentNumber slot 6
Module identification number for slot 6.
Unsigned32
Содержание SITOP PSU8600
Страница 404: ...Technical data 9 9 Dimension drawings Power supply system SITOP PSU8600 404 Manual 09 2018 A5E36758446 5 76 ...
Страница 410: ...Safety approvals EMC 10 4 EMC Power supply system SITOP PSU8600 410 Manual 09 2018 A5E36758446 5 76 ...
Страница 418: ...Environment Power supply system SITOP PSU8600 418 Manual 09 2018 A5E36758446 5 76 ...