Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
318
Manual, 09.2018, A5E36758446-5-76
Display name
Data type
Definition
Description
Alarm_F_UnknownModuleDetectedSlot5 Boolean
Sitop_8600_AlarmType
Unknown module found (slot 5).
Alarm_F_UnknownModuleDetectedSlot6 Boolean
Sitop_8600_AlarmType
Unknown module found (slot 6).
Alarm_F_UzkHigh
Boolean
Sitop_8600_AlarmType
The voltage on the internal power
bus is too high (possibly because
power is being fed back into the
device - or because of a defect) All
outputs are switched off.
Alarm_F_WrongChecksum
Boolean
Sitop_8600_AlarmType
Incorrect checksum of software in
the device. The corresponding
device is now in the bootloader,
and must be reactivated using a
firmware update.
Alarm_F_WrongExtensionModuleNum-
ber
Boolean
Sitop_8600_AlarmType
Invalid number of expansions. The
slot number is not valid
Alarm_MD_DeviceOvertemperature
Boolean
Sitop_8600_AlarmType
Overtemperature condition in a part
of the device. The temperature lies
above the alarm threshold, but
below the safety threshold. The
device continues to operate nor-
mally.
Alarm_MD_General
Boolean
Sitop_8600_AlarmType
General critical error. In normal
operation, the device of functions
correctly. However, the response in
the case of operating situations,
which do not correspond to normal
operation under nominal limits, can
deviate from the expected or the
configured response.
Alarm_MD_LessCapableModuleDetec-
ted
Boolean
Sitop_8600_AlarmType
Module with reduced power de-
tected.
Alarm_MD_ModuleParametersCorrupt
Boolean
Sitop_8600_AlarmType
The stored module configuration is
incorrect/corrupt. The device con-
tinues to operate consistently.
Alarm_MD_Phasefail
Boolean
Sitop_8600_AlarmType
A phase failure due to the failure of
a supply cable was detected. The
device state still lies within the
defined load and/or time profile for
this fault. The device continues to
operate normally.
Alarm_MD_PowerbusHighResistant
Boolean
Sitop_8600_AlarmType
The internal power bus has a high
resistance. It is possible that a plug
connection has not been correctly
inserted.
Alarm_MD_Supplylimits
Boolean
Sitop_8600_AlarmType
Supply voltage is outside the nomi-
nal limits. Automatic derating (li-
mited performance) can occur
when the voltage is low.