Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
283
Procedure
1.
Select menu "Diagnostics".
2.
Select submenu "Online functions".
3.
Select entry "Output ON/OFF".
4.
In the editor area, click on "Reset of all outputs".
5.
Acknowledge the confirmation prompt with "OK".
Buffering on/off
Only available if there is at least one buffer module or one UPS module in the system.
You can activate/deactivate system buffering using the "Buffering on/off" function.
If you switched off the buffer component using function "Buffering on/off" then checkbox
"Buffer component disabled via control command" is activated.
Battery capacity test
Only available if there is at least one UPS module with at least one connected battery
module in the system.
The test to measure the battery capacity is started using the "Start capacity measurement"
function.
Before starting the test, you will be requested to ensure a minimum system load of 120 W.