Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
234
Manual, 09.2018, A5E36758446-5-76
Slot
Subslot Data
Description
Value range
Data size
1-6
9
Channel8 Utarget
[10 mV]
see data "Channel 1"
Channel8 Ilimit
[10 mA]
Channel8 Ithreshold
Channel8
OutputEnable
Channel8 Reset_In
Data block active
Output data SITOP UPS8600
Slot
Subslot Data
Description
Value range
Data size
1-6
1
Maximum charging
power
Maximum charging power
0 (Off), 1 (Low), 2
(High)
(Default setting: 2)
Unsigned8
Data block active
Indicator: Data block contains valid
data.
0 = false, >0 = true
(default setting: false)
Unsigned8
7.6.1.3
Operating states SITOP PSU8600
Operating state of the power supply system (device operating state)
Status message
Description
0 = Off
Power supply system is shut down.
1 = ErrorOff
The power supply system was automatically switched off due to operation under impermis-
sible operating conditions.
2 = ReadyForRestart
After an automatic shutdown due to a fault, the power supply system can be reactivated by
switching off and switching on the supply voltage.
3 = Boot
The power supply system is starting up, all outputs are still switched off.
4 = Running
The power supply system is in normal operation.
5 = Phasefail
Phase failure of the supply voltage detected. The power supply system can continue to
operate in the normal mode without any restrictions for a limited period of time.
6 = SystemOverload (IP)
System overload within the permissible overload profile detected. The power supply system
continues to operate in normal mode.
7 = SystemOverload (OP)
System overload outside the permissible overload profile detected. The power supply sys-
tem can only operate with restrictions.
8 = SystemOverload (PL)
Very high, transient peak load detected. The power supply system is in normal operation.
9 = Buffering
Primary supply voltage has failed. The power supply system is in buffer mode.
10 = SystemOverload (IP)
during buffering
System overload within the permissible overload profile detected. The power supply system
continues to operate in buffer mode.
11 = SystemOverload (OP)
during buffering
System overload outside the permissible overload profile detected. The power supply sys-
tem can only operate with restrictions.
12 = SystemOverload (PL)
during buffering
Very high, transient peak load detected. The power supply system is in buffer mode.