Engineering and remote access
7.10 Parameter write behavior of the SITOP PSU8600
Power supply system SITOP PSU8600
352
Manual, 09.2018, A5E36758446-5-76
Index 54: OPC UA settings (reading/writing)
Data
Description
Data type
OPC UA server enabled
Activate/deactivate the OPC UA interface of the
SITOP PSU8600:
•
0: disable
•
255: enable
Unsigned8
Unencrypted access enabled
Activate/deactivate unencrypted access via the
OPC UA interface of the SITOP PSU8600:
•
0: disable
•
255: enable
Unsigned8
OPC UA server port
Set port for OPC UA interface (1 to 65535)
Unsigned16
Index 55: NTP client settings (reading/writing)
Data
Description
Data type
NTP client enabled
Activate/deactivate NTP client:
•
0: disable
•
255: enable
Unsigned8
Padding
Fill byte(s)
Unsigned8
NTP server address 1
IP address of NTP server 1
String[16]
NTP server address 2
IP address of NTP server 2
String[16]
NTP server address 3
IP address of NTP server 3
String[16]
NTP server address 4
IP address of NTP server 4
String[16]
Index 57: ProfiNet security enhancement settings (reading/writing)
Index for the data: Index 55
Data
Description
Data type
DCP Readonly enabled
Unsigned8
Padding
Fill byte(s)
Unsigned8
Содержание SITOP PSU8600