Mounting and maintenance
4.2 Rail mounting
Power supply system SITOP PSU8600
118
Manual, 09.2018, A5E36758446-5-76
4.2
Rail mounting
Basic unit
WARNING
Risk of electric shock
Before starting any mounting/installation work, the main switch of the system must be
opened and measures taken to prevent it from being reclosed. If this instruction is not
observed, touching live parts can result in death or serious injury.
When installing in a control cabinet, the basic unit can be snapped onto standard mounting
rails, see Chapter "Mechanical system (Page 398)".
1.
Position the device with the mounting rail guide at the upper edge of the standard
mounting rail and press down to lock it into place.
2.
If it is difficult to snap it into place, simultaneously press the slider using a screwdriver.