Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
265
Index 32: State information (reading)
Data
Description
Data type
Actual Charging Power
[10mW]
Actual charging power
Unsigned16
Maximum permitted
charging power
Maximum permitted
charging power
0 = Off
Module is not charged
Unsigned8
1 = Low
60 W charging power
2 = High (default set-
ting)
120 W charging power
State of Charge [%]
Charge status
Unsigned8
Module operation state Operating state
0 = Off
UPS module is in the
"Off" operating state.
Unsigned8
1 = Boot
UPS module is presently
booting.
2 = Default
Complete buffer readi-
ness: The energy storage
device of the UPS module
is fully charged (normal
operation).
3 = Buffering
UPS module is in the
buffer mode: The power
supply system is supplied
via the UPS module.
4 = ErrorOff
Shutdown after error: An
error occurred when op-
erating the UPS module.
The UPS module is not
operational and must be
restarted by switching off
the supply voltage and
switching it on again.
5 = ReadyForRestart
UPS module is ready to
be switched on again
8 = Disable
UPS module is deactivat-
ed
9 = FWUpdate
A firmware update is
presently being per-
formed.
The basic unit generates
the signal.
10 = Buffer End
End of buffering
11=BatteryTest
Battery test is being car-
ried out
Fill byte(s)
-
Unsigned8
Battery state
Operating state of the
connected battery mod-
ules
0 = Off
UPS module is in the
"Off" operating state.
Unsigned8
1 = Boot
UPS module is presently
booting.