Operator control at the device
3.7 Setting the on delay
Power supply system SITOP PSU8600
96
Manual, 09.2018, A5E36758446-5-76
No on delay
With the power supply system shut down, bring both DIP switches "STDA" and "STDB" into
position "OFF" (left), to deactivate on delay.
STDA
STDB
25 ms on delay
With the power supply system shut down, bring DIP switch "STDA" into position "ON" (right)
and "STDB" into position "OFF" (left) in order to set the on delay to 25 ms.
STDA
STDB
100 ms on delay
With the power supply system shut down, bring DIP switch "STDA" into position "OFF" (left)
and "STDB" into position "ON" (right) in order to set the on delay to 100 ms.
STDA
STDB
Load-optimized on delay
With the power supply system shut down, bring both DIP switches "STDA" and "STDB" into
position "ON" (right) to activate load-optimized on delay.
STDA
STDB