Operator control at the device
3.5 Prioritization when the line supply fails
Power supply system SITOP PSU8600
92
Manual, 09.2018, A5E36758446-5-76
All outputs have the same priority during buffering
With the power supply system shut down, bring DIP switch "PRY 1" into position "OFF" (left),
so that all outputs have the same priority when buffering is required.
Prioritizing output 1 during buffering
With the power supply system shut down, bring DIP switch "PRY 1" into position "ON" (right),
so that output 1 of the basic unit has priority when buffering is required.
WARNING
Death or serious injury can occur when the outputs are suddenly switched-on!
Outputs 2 ... n, which are switched off when the power fails as output 1 has priority, are
automatically switched-on again when the line supply returns.
•
Lock-out the connected loads so they cannot inadvertently start.