Buffering
Parameter
Value range
Default setting
Buffer component disabled via control command
Yes/no
No
Threshold value for sufficient buffer readiness
10 - 90 %
85 %
Short time interruption at output 1 is enabled
Yes/no
No
Dead time until start of short-time interruption sequence
0 - 3 600 000 000 ms 3 000 ms
Waiting time up to short time interruption
0 - 3 600 000 000 ms 15 000 ms
Duration of short time interruption
0 - 3 600 000 000 ms 5 000 ms
Waiting time after client shutdown completed
0 - 3 600 000 000 ms 3 000 ms
Preferred buffer component if the power supply voltage
fails
•
Alternating dis-
charge
•
UPS8600[1]
•
UPS8600[2]
Alternating
discharge
Preferred charging mode for a system start
Yes/no
No
Only switch-on one output after starting from the battery
Yes/no
No
Examples for conversion
ms (milliseconds)
s (seconds)
m (minutes)
3 000
3
5 000
5
15 000
15
¼
60 000
60
1
300 000
300
5