Safety, approvals, EMC
10.4 EMC
Power supply system SITOP PSU8600
408
Manual, 09.2018, A5E36758446-5-76
10.4
EMC
Basic units
6EP3436-8SB00-2AY0
6EP3437-8SB00-2AY0
UPS module
6EP4197-8AB00-0XY0
Expansion modules
6EP4436-8XB00-0CY0
6EP4437-8XB00-0CY0
6EP4436-8XB00-0DY0
Buffer modules
6EP4297-8HB00-0XY0
6EP4297-8HB10-0XY0
6EP4293-8HB00-0XY0
6EP4295-8HB00-0XY0
Generic standards
EN 61000-6-2
Noise immunity for industrial environments
EN 61000-6-3
Emission for residential areas
Emitted interference EN 55022
Class B
Line harmonics limit EN 61000-3-2
Class A
Electrostatic dis-
charge
EN 61000-4-2
8 kV contact, 8 kV air
Electromagnetic
fields
EN 61000-4-3
80 - 1000 MHz: 10 V/m
1.4 - 2.0 GHz: 10 V/m
2.0 - 2.7 GHz: 1 V/m
High-speed transient
disturbance variables
(burst)
EN 61000-4-4
4 kV at line connections
2 kV at DC output
Surge voltages
EN 61000-4-5
2 kV symmetrical at line connections
6 kV unbalanced at the line supply connections
0.5 kV balanced/unbalanced on DC output cables
High-frequency fields EN 61000-4-6
10 kHz - 80 MHz: 10 V/m
Battery modules
6EP4143-8JB00-0XY0
6EP4145-8GB00-0XY0
Generic standards
EN 61000-6-2
Noise immunity for industrial environments
EN 61000-6-3
Emission for residential areas
Emitted interference EN 55022
Class B
Содержание SITOP PSU8600
Страница 404: ...Technical data 9 9 Dimension drawings Power supply system SITOP PSU8600 404 Manual 09 2018 A5E36758446 5 76 ...
Страница 410: ...Safety approvals EMC 10 4 EMC Power supply system SITOP PSU8600 410 Manual 09 2018 A5E36758446 5 76 ...
Страница 418: ...Environment Power supply system SITOP PSU8600 418 Manual 09 2018 A5E36758446 5 76 ...