Troubleshooting
8.3 Alarm list web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
367
ID
Severity
Event
Help text
65
N
Parameter out of permissible value
range.
A control command is attempting to set a value outside the
value range that the hardware module can implement. The
value is automatically limited to the minimum or maximum
permitted value for the module.
90
MR
Output 1 interruption: Shutdown
initiated
The shutdown of output 1 has been initiated in the course of
the output 1 interruption sequence.
91
MR
Shutdown due to system overload. System load current is outside the permissible overload
profile.
92
F
System safety shutdown due to
critical load difference between AC
input and outputs.
Critical load difference between the AC input and the out-
puts. The initiated safety shutdown will turn off the device
immediately.
93
F
System safety shutdown due to
significant load difference between
AC input and outputs.
Out of range difference between AC input and outputs. Turn
power off and on to reactivate the system.
94
N
System restart completed after
safety shutdown.
System restart completed after safety shutdown.
95
F
Ready for restart after critical load
condition.
Ready for restart after safety shutdown because of critical
load current. Turn power off and on to reactivate the system.
96
F
Ready for restart after out of profile
peak load.
Ready for restart after safety shutdown because out of pro-
file peak load.
97
MD
Error while reading system configu-
ration from internal memory.
Error while reading system configuration from internal
memory. The system is started with factory settings.
98
MR
Input voltage below permitted
range.
Input voltage below permitted range.
99
MR
Input voltage above permitted
range.
Input voltage above permitted range.
100
MR
Safety shutdown of internal primary
supply unit
Safety shutdown of internal primary supply unit
152
N
Client shutdown finished (start of
ping signal)
The shutdown sequence for the connected client was start-
ed. The sequence will now run independently of any opera-
tion to return the supply.
153
N
Client shutdown initiated (end of
ping response)
The connected client has completed its shutdown operation.
The output can now be switched off.
154
MR
Buffers empty, buffering not possi-
ble
Buffering mode is not possible due to low charge
155
N
Insufficient charge level
The battery charge level is too low to guarantee the config-
ured buffer capacity.
156
N
Buffering disabled by command
Buffer component disabled via control command
157
N
Charging disabled by command
Charging is disabled through control command.
158
N
Charging restricted due to system
overload
Charging of the system buffering components has been
limited due system overload.
Содержание SITOP PSU8600
Страница 404: ...Technical data 9 9 Dimension drawings Power supply system SITOP PSU8600 404 Manual 09 2018 A5E36758446 5 76 ...
Страница 410: ...Safety approvals EMC 10 4 EMC Power supply system SITOP PSU8600 410 Manual 09 2018 A5E36758446 5 76 ...
Страница 418: ...Environment Power supply system SITOP PSU8600 418 Manual 09 2018 A5E36758446 5 76 ...