background image

Altronix Corp.

140 58th St. Brooklyn, NY

eFlow104N/

eFlow104NX

  - 10A @ 24VDC

eFlow104N8/

eFlow104NX8

  - 10A @ 24VDC
  - Eight (8) Fused Outputs

eFlow104N16/

eFlow104NX16

  - 10A @ 24VDC
  - Sixteen (16) Fused Outputs

eFlow104N8D/

eFlow104NX8D

  -  10A @ 24VDC
  -  Eight (8) PTC Protected 
    Class 2 Power-Limited Outputs

eFlow104N16D/

eFlow104NX16D

  -  10A @ 24VDC
  -  Sixteen (16) PTC Protected 
    Class 2 Power-Limited Outputs

eFlow104N Series

Power Supply/Chargers

Models Include:

Rev. 104NRP021119

More than just power.

TM

Installing Company:  _______________ Service Rep. Name:  __________________________________  

Address:  _____________________________________________  Phone #:  __________________

Installation Guide

Содержание eFlow 104N Series

Страница 1: ...ht 8 PTC Protected Class 2 Power Limited Outputs eFlow104N16D eFlow104NX16D 10A 24VDC Sixteen 16 PTC Protected Class 2 Power Limited Outputs eFlow104N Series Power Supply Chargers Models Include Rev 104NRP021119 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ______________...

Страница 2: ...w104NX eFlow104N8 eFlow104NX8 eFlow104N16 and eFlow104NX16 The following units provide Class 2 power limited outputs eFlow104N8D eFlow104NX8D eFlow104N16D and eFlow104NX16D If a power limited output is required in the end product application the DC output from the power supply must be connected to a separately Listed control unit or accessory board that provides power limited outputs The product s...

Страница 3: ...C 60Hz Input Battery Wires Minimum 0 25 spacing must be provided CAUTION Do not touch exposed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified service personnel For Fire Alarm applications the outputs are Special Applications only see list refer to Appendix A pg 12 Input 120VAC 60...

Страница 4: ... position Fig 1c pg 5 9 Trigger terminals are end of a line resistor supervised 10k ohms Opening or shorting trigger terminals will cause DC output to shutdown Fig 1d pg 5 10 Place a jumper for non latching FACP A momentary short on these terminals resets FACP latching Trigger EOL Shutdown Fig 1e pg 5 11 For Access Control Applications mount UL Listed tamper switch Altronix model TS112 or equivale...

Страница 5: ... power is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maximum charge current 1 0A non power limited Fig 1g pg 5 Power Distribution Module Terminal Legend PD8UL PD8ULCB Terminal Legend PD16W PD16WCB Function Description 1P to 8P 1P to 16P Positive DC power o...

Страница 6: ... Power Limited Outputs N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply Board Factory Installed Replace fuses with the same type and rating 3 5A 250V N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs Fro...

Страница 7: ...L294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION Power supply board is factory set for 24VDC Use two 2 12VDC stand by batteries Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 7AH Rechargeable batteries are the largest batteries that can fit in this enclosure A UL Listed external battery enclosure must be used ...

Страница 8: ...e employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian installations use shielded wiring for all connections Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 6a Fig 6 Fig 6a Outputs are non power limite...

Страница 9: ...e minimum 0 25 spacing 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure A UL listed external battery enclosure must be used if using 40AH or 65AH batteries Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations Optional Rechargeable Stand by Battery for UL294 Applications Note 12V...

Страница 10: ... employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian installations use shielded wiring for all connections Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 8a Fig 8 Fig 8a Outputs are non power limited...

Страница 11: ...m x 82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm 6 5625 166 7mm 3 25 82 6mm 3 25 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 13 0 330 2mm 5 10 129 5mm 1 20 30 5mm ...

Страница 12: ...125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 eFlow104NX eFlow104NX8 eFlow104NX8D eFlow104NX16 eFlow104NX16D 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm ...

Страница 13: ...lectric w 135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 0 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 0 05 23 4WTA B 12 24 volt I3 Photo w Therm Sounder 0 05 35 4WTR B...

Страница 14: ...remote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state change and unit temperature Access control and user managment Restrict read write Restrict users to specific resources Two 2 integral network controlled Form C Relays Three 3 programmable inpu...

Страница 15: ...x is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIeFlow104N Series G26U MEMBER Notes ...

Страница 16: ...65AH 6A 10A 1 5A 10A Over 4 Hours 10A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 0A Automatic switch over to stand by battery when AC fails Transfer to stand by battery power is instantaneous with no interruption LED Diagnostics Red DC Green AC AC1 Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery is sup...