CUT ALONG DOTTED LINE
Power Supply/Chargers Operating Guide
Models Include:
Model
Input
120VAC,
60Hz
Output
Auxiliary Power-Limited
Output (unswitched)
Ripple
Voltage
12VDC
24VDC
eFlow104N,
eFlow104N8, eFlow104N8D,
eFlow104N16, eFlow104N16D
4.5A
–
10A
1A
700mV
eFlow104NX,
eFlow104NX8, Flow104NX8D,
eFlow104NX16, eFlow104NX16D
Overview:
The eFlow104N series power supply/chargers convert a 120VAC, 60Hz input to a 24VDC output.
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications Stand-by
7AH
0.4A/10A
N/A
5 Mins./10A
12AH
1A/10A
0.3A/10A
15 Mins./10A
40AH
6A/10A
1.2A/10A
Over 2 Hours/10A
65AH
6A/10A
1.5A/10A
Over 4 Hours/10A
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.0A.
• Automatic switch over to stand-by battery when AC fails.
Transfer to stand-by battery power is instantaneous with no interruption.
LED Diagnostics:
Red (DC)
Green (AC/AC1) Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery is supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Installing Company: _______________ Service Rep. Name: __________________________________
Address: _____________________________________________ Phone #: __________________
Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow104N Series, Rev. 104NRP021119 for
complete instructions. This sheet is to be removed, framed and posted next to the unit.
Rev. 104NRP021119