Description, device design, dimension drawing
2.8 Display elements
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
47
Table 2- 8
LEDs "SF"
③
and "RUN"
④
Signaling
LED "SF"
③
LED "RUN"
④
Off
Off
Device is OFF, or there is no connection to a
PROFINET IO controller
Off
Flashing green
(0.5/0.5)
Configuration by the PROFINET IO controller
Off
Green
Application started successfully, module OK
Red
Green
Application started successfully, module not OK
Flashing red (0.1/0.1)
Green
Application running, diagnostics can be called
Flashing red (0.5/0.5)
Off
Device identification requested via DCP
(LED flashes for 3 s)
Flashing red (0.5/0.5)
Flashing green
(0.5/0.5)
Firmware update
Table 2- 9
LEDs "P1, P2"
⑤
Signaling
Off
Device is OFF or is not connected with the IO controller
Green
Device is connected with IO controller, no activity.
Green/orange alternately
Device connected with the IO controller, send/receive data (RX/TX).