Description, device design, dimension drawing
2.6 Connections and terminal designations
Power supply system SITOP PSU8600
38
Manual, 09.2018, A5E36758446-5-76
2.6.5
Battery modules
The power cables to the UPS module and to additional battery modules are connected at
power terminals
①
. Refer to the diagram in Section "Description of the UPS module
(Page 26)". The data cables to the UPS module and to additional battery modules are
connected at communication terminals
②
.
NOTICE
Material damage
It is not permissible that the "+" and "-" power terminals are connected to the "0V", the 0V
busbar or "GROUND".
Note
Use cables with the same length and the same cross-section.
Dimension the power cables corresponding to the fuse in the battery module.
The fuse should only be inserted in the fuse holder when commissioning the device.
Connections and terminal designations
①
Power terminals "-" and "+"
Plug-in terminal each with a screw connection
②
Communication terminals "COM2", "COM1"
Plug-in terminal each with a screw connection
See the diagram in Section "Description of the battery modules (Page 28)".
Terminal data 6EP4143-8JB00-0XY0, 6EP4145-8GB00-0XY0