Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
236
Manual, 09.2018, A5E36758446-5-76
Operating state, output 1 … n (channel1 … n operating state)
The status messages of an output are listed in the table below. The data applies to outputs 1
to n.
Status message
Description
0 = ManualOff
Output switched off manually (button): The output was manually switched off using the
button on the device. The device can only be switched on manually using the button on the
device.
1 = RemoteOff
Output switched off (PROFINET/IE): The output was remotely switched off via
PROFINET/IE.
2 = BufferOff
Output switched off (prioritization output 1): The output was switched off during buffering.
3 = OverLoadOff
Output switched off (overload): Invalid overload occurred at the output. The output was
switched off.
4 = ReadyForRestart
Output ready for reset (reset): Output is ready to be switched on again after automatic over-
load shutdown.
5 = ErrorOff
Output switched off (error)
6 = Boot
Output switched off (startup)
7 = Running
Output switched on (normal operation)
8 = OverLoad
Output in overload operation: The output current is above the specified response threshold,
but still within the permissible overload profile.
9 = Limit
Output current limited to the response threshold: The output is in the overload mode. The
output current is limited to the configured response threshold.
10 = OverloadWithDerating Output in overload operation (system overload)
11 = LimitWithDerating
Output current limited (system overload)
12 = Locked
Output switched off as the UPS8600 is being charged
7.6.1.5
Operating states SITOP BUF8600
Operating state of the buffer module (buffer operating state)
Status message
Description
0 = Off
Buffer component is in the "Off" operating state.
1 = Boot
Buffer component is powering up.
2 = Full
Complete buffer readiness: The energy storage device of the buffer component is fully
charged (normal operation).
3 = Buffering
The buffer component is operating in the buffer mode: The power supply system is supplied
via the buffer component(s).
4 = ErrorOff
Shutdown after error: A fault/error has occurred when operating the buffer component. The
buffer component is not operational and must be restarted by switching off the supply volt-
age and switching it on again.
5 = ReadyForRestart
Ready for a new start
6 = NotFully
ChargedReady
Ready for buffer operation as the energy storage device of the buffer component has been
sufficiently charged, but has not been fully charged.
7 = NotFully
ChargedNotReady
Not ready for buffering as the energy storage device of the buffer module has not been
sufficiently charged and is presently being charged.
8 = Disable
Buffer component is deactivated.
9 = FwUpdate
Firmware is being updated
10 = BufferEnd
Buffering ended