Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
329
ActualUpdateState
Display name
Data type
Definition
Description
UpdateProgress
UInt32
AnalogItemType
Firmware update progress
(0 - 100 %)
UpdateState
UInt32
AnalogItemType
Status or result of the ongoing or
completed firmware update:
0: Firmware is being updated
1: The file download was exited,
the system must be restarted to
initiate the internal update process.
2: The data format of the update
file was not accepted.
3: The update file is too big.
4: The update file does not match
this device.
5: The device is in the buffer mode,
and cannot be updated at the pre-
sent time.
Alarm
Display name
Data type
Definition
Description
Alarm_F_BufferNotReady
Boolean
Sitop_8600_AlarmType
Not ready for buffering. Energy
storage voltage is too low.
Alarm_F_CommunicationToModule Boolean
Sitop_8600_AlarmType
Communication with the expansion
module is faulty. All outputs on the
expansion module have been
switched off.
Alarm_F_General
Boolean
Sitop_8600_AlarmType
General error
Alarm_F_IncompatibleModuleDe-
tected
Boolean
Sitop_8600_AlarmType
The module has a module type that
is incompatible with the configura-
tion. The module cannot be com-
missioned.
Alarm_F_ModuleDefect
Boolean
Sitop_8600_AlarmType
A hardware failure has occurred.
All outputs of the power supply
system have been switched off.
Alarm_F_ModuleParameters
Corrupt
Boolean
Sitop_8600_AlarmType
Stored module configuration is
corrupt. The module cannot start
up correctly.
Alarm_F_Overtemperature
Boolean
Sitop_8600_AlarmType
Shutdown due to overtemperature.
Buffer component disabled.
Alarm_F_OvertemperatureModule Boolean
Sitop_8600_AlarmType
Shutdown due to overtemperature.
Buffer component disabled.
Alarm_F_SoftwareUpdating
Boolean
Sitop_8600_AlarmType
Performing firmware update.
Read/write access is currently not
possible.
Alarm_F_UnexpectedEmptySlotDe-
tected
Boolean
Sitop_8600_AlarmType
Unexpected empty slot detected
Содержание SITOP PSU8600
Страница 404: ...Technical data 9 9 Dimension drawings Power supply system SITOP PSU8600 404 Manual 09 2018 A5E36758446 5 76 ...
Страница 410: ...Safety approvals EMC 10 4 EMC Power supply system SITOP PSU8600 410 Manual 09 2018 A5E36758446 5 76 ...
Страница 418: ...Environment Power supply system SITOP PSU8600 418 Manual 09 2018 A5E36758446 5 76 ...