Operator control at the device
3.12 Setting the charging power of the UPS module
Power supply system SITOP PSU8600
104
Manual, 09.2018, A5E36758446-5-76
Note
If the power supply system is completely utilized by the loads connected at the outputs, then
there is no charging operation for the battery module connected to the UPS module.
Note
Charging is stopped for ambient temperatures of the BAT8600 Pb and BAT8600 LiFePO4
battery modules > 50 °C.
At ambient temperatures of the BAT8600 Pb battery modules between 40 °C and 50 °C, the
charge power is automatically reduced down to 60 W if only one battery module is connected
to the UPS module.
Note
Carefully note that the battery module temperature can increase due to charging and buffer
operations, even at lower ambient temperatures. This can result in the charge power been
reduced or shut down as a result of the temperature monitoring inside the battery module.