Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
330
Manual, 09.2018, A5E36758446-5-76
Display name
Data type
Definition
Description
Alarm_F_UzkHigh
Boolean
Sitop_8600_AlarmType
Voltage of the internal supply is too
high. All outputs of the power sup-
ply system have been switched off.
AlarmF_WrongChecksum
Boolean
Sitop_8600_AlarmType
Defective firmware detected. De-
vice must be reactivated with a
new firmware update.
Alarm_MD_General
Boolean
Sitop_8600_AlarmType
General critical error occurred. The
device may therefore behave in-
consistently.
Alarm_MD_LessCapableModule
Detected
Boolean
Sitop_8600_AlarmType
A module with reduced power was
detected. Deviating system behav-
ior may be possible.
Alarm_MD_ModuleParameters
Corrupt
Boolean
Sitop_8600_AlarmType
Stored module configuration is
corrupt. Deviating module behavior
may be possible.
Alarm_MD_Overtemperature
Boolean
Sitop_8600_AlarmType
Danger of overtemperature detect-
ed in a system component. Imme-
diate load reduction is
recommended.
Alarm_MD_OvertemperatureMo-
dule
Boolean
Sitop_8600_AlarmType
Danger of overtemperature detect-
ed in a system component. Imme-
diate load reduction is
recommended.
Alarm_MR_BufferStateBuffering
Boolean
Sitop_8600_AlarmType
The power supply system is sup-
plied via the buffer expansion
module(s).
Alarm_MR_General
Boolean
Sitop_8600_AlarmType
General error occurred. Device
behavior remains consistent, how-
ever.
Alarm_MR_ModuleParameters
Corrupt
Boolean
Sitop_8600_AlarmType
Stored module configuration is
corrupt. Module behavior remains
consistent, however.
Alarm_MR_MoreCapableModule
Detected
Boolean
Sitop_8600_AlarmType
A module with excessive power
was detected. Normal operation of
the system is possible.
Alarm_MR_NewModuleDetected
Boolean
Sitop_8600_AlarmType
New unconfigured module detected
Alarm_MR_SerialNumberDiverge
Boolean
Sitop_8600_AlarmType
Different serial number detected
Alarm_MR_UnexpectedModule
Detected
Boolean
Sitop_8600_AlarmType
Unexpected module type detected.
Alarm_N_BufferStateFull
Boolean
Sitop_8600_AlarmType
Ready for buffering. Energy stor-
age fully charged.
Alarm_N_BufferStateNotFull
Boolean
Sitop_8600_AlarmType
Restricted buffer capacity. Energy
storage not fully charged.
Alarm_N_BufferStateNotReady
Boolean
Sitop_8600_AlarmType
No buffer capacity. Energy storage
not sufficiently charged.
Alarm_N_SoftwareDownload
Boolean
Sitop_8600_AlarmType
Firmware was downloaded
Alarm_N_SoftwareVersionDiverge Boolean
Sitop_8600_AlarmType
Different firmware version detect-
ed.