Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
326
Manual, 09.2018, A5E36758446-5-76
Display name
Data type
Definition
Description
Alarm_MD_ChannelOverload
Boolean
Sitop_8600_AlarmType
Overload detected at the output
Alarm_MD_ChannelOvertempera-
ture
Boolean
Sitop_8600_AlarmType
Advance warning against overheat-
ing at output.
Alarm_MR_ChannelOverload
Boolean
Sitop_8600_AlarmType
The actual value of the output
current is above the set advance
warning threshold.
Alarm_MR_ChannelStateBuffered
Off
Boolean
Sitop_8600_AlarmType
Output switched off during buffer-
ing
Alarm_MR_ChannelStateCurrent
LimitOperation
Boolean
Sitop_8600_AlarmType
Current limit on the output after
occurrence of an overload
Alarm_MR_ChannelStateReadyFor
Restart
Boolean
Sitop_8600_AlarmType
Output is ready to be switched on
Alarm_N_ChannelOutputTurnedOff Boolean
Sitop_8600_AlarmType
Output was switched off.
Alarm_N_ChannelOutputTurnedOn Boolean
Sitop_8600_AlarmType
Output was switched on.
Alarm_N_ChannelStateManualOff Boolean
Sitop_8600_AlarmType
Output was switched off manually.
Alarm_N_SetpointParameterOutOf
Range
Boolean
Sitop_8600_AlarmType
Parameter out of permissible value
range.
HardwareSettings
Display name
Data type
Definition
Description
HardwareCurrentLimitPotentiome-
ter
Float
AnalogItemType
Manually set response threshold
HardwareOutputEnableButton
Boolean
PropertyType
Output switched off manually (but-
ton):
HardwareTargetVoltagePotentiom-
eter
Float
AnalogItemType
Manually set setpoint of the output
voltage.
RemoteTargetValues
Display name
Data type
Definition
Description
CurrentLimitManToRem
Method
-
Set response threshold
CurrentLimitSetpoint
Float
AnalogItemType
Response threshold of the output
current
CurrentThresholdSetpoint
Byte
AnalogItemType
Prewarning threshold output cur-
rent
OutputEnableSetpoint
Boolean
PropertyType
Switch on output
OutputOperationModeSetpoint
Byte
MultiStateDiscrete-
Type
Operating mode
OutputReset
Method
-
Reset
StartupDelaySetpoint
UInt16
AnalogItemType
On delay
TargetVoltageManToRem
Method
-
Accepts the manually set output
voltage setpoint in the remote set-
ting
TargetVoltageSetpoint
Float
AnalogItemType
Setpoint output voltage