Engineering and remote access
7.8 OPC UA server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
321
7.8.6.5
Buffering
Display name
Data type
Definition
Description
BufferDeadtimeBuffering
ModeAlarmSetpoint
UInt32
AnalogItemType
Dead time for buffering mode alarm
BufferDisableSetpoint
Boolean
PropertyType
Deactivates the buffering if set to
TRUE.
BufferDurationShorttimeInterrup-
tionSetpoint
UInt32
AnalogItemType
Duration of short-time interruption
BufferLonglifeOperationEnableSet-
point
Boolean
PropertyType
LONGLIFE operating mode acti-
vated
BufferReadyThresholdSetpoint
Byte
AnalogItemType
Threshold value for sufficient buffer
readiness
BufferShorttimeInterruptionEna-
bleSetpoint
Boolean
PropertyType
Short-time interruption at output 1
is enabled
BufferWaittimeShorttimeInterrup-
tionSetpoint
UInt32
AnalogItemType
Waiting time until transient interrup-
tion
BufferWaitTimeClientShutdown-
Setpoint
UInt32
AnalogItemType
Wait time after shutting down the
client ended
BufferDischargeSequenceSelec-
tionSetpoint
Byte
AnalogItemType
Discharge selection
•
0 … alternating discharge
•
1 … UPS8600[1]
•
2 … UPS8600[2]
BufferChargeBeforeOutputEnable-
Setpoint
Boolean
PropertyType
Charge the buffer components
before activating the outputs
BufferStartOnlyOut-
put1FromBatterySetpoint
Boolean
PropertyType
When starting from the battery,
only switch on output 1
7.8.6.6
General
Display name
Data type
Definition
Description
DeviceCurrentThresholdSetpoint
Byte
AnalogItemType
Threshold for system output cur-
rent prewarning
DeviceManualCurrent
ThresholdSetpoint
Byte
AnalogItemType
General prewarning threshold for
individual output current in
MANUAL mode
DevicePowerSupplyFailureDead-
TimeSetpoint
UInt16
AnalogItemType
Dead time for alarm message 'In-
put voltage outside permitted
range'
DevicePrioritizedBuff-
eringOutput1EnableSetpoint
Boolean
PropertyType
Prioritized buffering of output 1.
DeviceSoftOutputCharacteris-
ticSetpoint
Boolean
PropertyType
Soft output characteristic
DeviceStartupModeSetpoint
Byte
MultiStateDiscrete-
Type
System start characteristics.
DeviceSystemOv-
erloadAlarmDeadTimeSetpoint
UInt16
AnalogItemType
Dead time for system output cur-
rent prewarning.