Description, device design, dimension drawing
2.8 Display elements
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
57
2.8.5
Battery modules
No.
Labeling
Signal type
Signaling
①
O.K.
LED
Device status
States of the LEDs
Table 2- 16 LED "O.K."
①
Signaling
Green
Battery module fully charged
Flashing green (1/1)
Battery module is being charged, buffer mode possible
Flashing green (0.25/0.25)
Battery module being charged, charge state insufficient for buffer operation
Flashing yellow (1/1)
•
Battery module temperature is outside the permissible range
•
Interrupted communication cable
Restricted charge operation, buffer operation is possible
Flashing yellow (0.25/0.25)
The end of the battery service life has been reached (according to EUROBAT
80% of the rated capacity), it is recommended that the batteries are replaced
Buffer mode is still possible
Red
Cyclic battery test is negative, batteries must be replaced
Buffer mode not possible
Flashing red (1/1)
Restoration mode after deep discharge, charge state insufficient for buffer opera-
tion
Flashing red (0.25/0.25)
•
Battery module connected with incorrect polarity, buffer mode not possible
•
Power connections interrupted or fuse defective/ruptured, buffer mode not
possible
•
While replacing the battery, request to immediately reset the lifetime counter
using the reset button
Alternating, green/red
(0.25/0.25 A for 5 s)
Battery replacement confirmed