Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
269
Index 32: State information (reading)
Data
Description
Data type
Capacity of the battery
[Wh]
Charge capacitance of the battery module
Unsigned16
State of health [%]
Result of the last battery test "state of health" (SoH)
Unsigned8
Module operation state Operating state
0 = Off
Battery module is in the
"Off" operating state.
Unsigned8
1 = Boot
Battery module is pres-
ently running up.
2 = Default
Complete buffer readi-
ness: The energy storage
device of the UPS module
is fully charged (normal
operation).
3 = Error Off
Battery module run down
after fault.
4 = ChargingRestrict-
ed
Battery charging is re-
stricted.
5 = EndOfLife-
timeReached
End of lifecycle has been
reached.
6 = MaintenaceRe-
quired
Maintenance required.
7 = Change completed Battery module success-
fully replaced.
8 = Battery defective
Battery module defective
9 = Not ready for buff-
ering
Battery module is not fully
charged and is not ready
for buffering.
10 = Not completely
loaded but ready for
buffering
Battery module is not fully
charged, but is ready for
buffering.
11 = Ready for buffer-
ing
Ready for buffering.
12 = DeepDischarge-
Recovery
Battery module was deep-
discharged and is in the
recovery phase.