Description, device design, dimension drawing
2.3 Description of the buffer modules
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
25
LONGLIFE mode
In order to increase the service life of the buffer modules equipped with double-layer
capacitors, these can be operated in the LONGLIFE mode with reduced buffer capacity.
When the buffer module is completely charged (LED "O.K." lights green) power failures of
3 s up to a maximum of 8 s can be buffered with a load current of 40 A. The LONGLIFE
mode can only be selected via the configuration (STEP 7, OPC UA server, web server).
You can find more information in Chapter "Engineering and remote access (Page 169)"