Troubleshooting
8.3 Alarm list web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
381
ID
Severity
Event
Help text
15
MD
Battery temperature too low, the
battery will not operate
The battery temperature is too low. The battery will not op-
erate in this situation. Buffering is no longer possible de-
pending on the number of connected batteries!
16
MR
Warning before battery low tem-
perature
Battery temperature too low - reduced output current
17
N
The calculated battery lifetime was
reset.
The battery lifetime counter has been reset after finished
battery pack change.
18
N
Battery replacement recommended
(end of lifetime approaching)
It is recommended to replace the battery because the bat-
tery lifetime is approaching its calculated end and there is a
threat of restricted buffer readiness.
19
MR
Battery replacement recommended
(end of lifetime reached)
It is recommended to replace the battery because the bat-
tery lifetime has reached its calculated end and restricted
buffer readiness is probable.
20
MD
Battery parameters corrupt
The battery configuration is corrupt. Battery behavior may
deviate.
21
MR
Battery parameters corrupt
The battery configuration is corrupt. The battery behavior
remains unchanged, however.
22
MR
Communication to battery inter-
rupted
Communication with the battery is interrupted. Buffering is
still possible, but the battery charge is reduced to a mini-
mum.
23
MR
The power line to the battery is
interrupted
The power line to the battery is interrupted. The battery can
no longer buffer or it can no longer be charged any more.
24
MR
Battery pack defective
The battery pack is probably defective and should be re-
placed to avoid buffering problems.