Description, device design, dimension drawing
2.8 Display elements
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
53
States of the individual LEDs
Table 2- 13 LED "O.K."
①
Signaling
Off
Device is OFF or is powering up (booting)
Green
Normal operation, module charged, complete buffer readiness
Flashing green (1/1)
Module is being charged, buffer readiness partially available.
Flashing green (0.25/0.25)
Module is being charged, buffer readiness not available
Red
•
ERROR OFF: Module automatically switched off due to overtemperature
basic unit, phase imbalance
•
Fault in the module or communication error to the basic unit
flashing red (1/1)
Module deactivated via ON/OFF contact or remote command (no buffering when
the power fails)
Flashing red (0.25/0.25)
•
Module ready for the automatic ERROR OFF shutdown to be reset – or after
a firmware update has been completed, by switching off the supply voltage
and switching it on again (power OFF/ON)
•
Charge is still available after power supply voltage OFF
•
Device shut down due to firmware update of another system component
•
Incorrect hardware configuration (REMOTE mode)
Yellow
Power failure, buffer mode active
Alternating, green/red
(0.25/0.25)
Firmware being updated
Содержание SITOP PSU8600
Страница 404: ...Technical data 9 9 Dimension drawings Power supply system SITOP PSU8600 404 Manual 09 2018 A5E36758446 5 76 ...
Страница 410: ...Safety approvals EMC 10 4 EMC Power supply system SITOP PSU8600 410 Manual 09 2018 A5E36758446 5 76 ...
Страница 418: ...Environment Power supply system SITOP PSU8600 418 Manual 09 2018 A5E36758446 5 76 ...